Battery pack calculator: series, parallel, energy and C-rating current

Series adds voltage, parallel adds capacity, and the C rating sets the current limit. Enter the cell and the layout to get the pack figures.

Nominal voltage: – V (full: – V)Capacity: – AhEnergy: – WhMax continuous current: – A

Use the continuous rating from the cell datasheet, not the peak. Keep margin, and use a proper battery management board.

How it is calculated

Pack voltage = cells in series × cell voltage. Pack capacity = cells in parallel × cell capacity. Energy in Wh = nominal voltage × capacity. Maximum continuous current = capacity in Ah × C rating.

A worked example

A 3S2P pack of 2.5 Ah cells at 3.7 V nominal gives 3 × 3.7 = 11.1 V nominal (12.6 V full), 2 × 2.5 = 5 Ah and 11.1 × 5 = 55.5 Wh. With a 10C rating the limit is 5 × 10 = 50 A.

Common mistakes

  • Treating the full-charge voltage as the working voltage.
  • Using the peak C rating as the continuous one.
  • Mixing old and new cells in one pack.

battery runtime calculator, robot battery guide, wheel speed calculator.

Last reviewed: November 2026. The calculator runs in your browser and sends nothing anywhere. Results are ideal-case figures; add margin before you order parts.

A second worked example

Take a 4S3P pack of 3.0 Ah cells with a nominal voltage of 3.6 V and a full voltage of 4.2 V per cell.

  • Nominal voltage = 4 × 3.6 = 14.4 V. Full voltage = 4 × 4.2 = 16.8 V.
  • Capacity = 3 × 3.0 = 9 Ah.
  • Energy = 14.4 × 9 = 129.6 Wh.
  • With a continuous rating of 2C: 9 × 2 = 18 A.

If a robot draws 36 W on average, an ideal runtime is 129.6 ÷ 36 = 3.6 hours. In practice you cannot use all the capacity, so plan for less.

How to read the notation

In 4S3P, S counts cells in series and P counts parallel cells per group, so the pack has 4 × 3 = 12 cells. Cells in series are connected end to end and add voltage. Cells in parallel are tied together and add capacity and current ability.

Assumptions and limits

  • Nominal voltage is an average; the real voltage drops as the cell discharges. Check the discharge curve in the cell datasheet and the lowest allowed cell voltage.
  • Rated capacity is measured at a particular discharge current. At a higher current the available capacity is often lower.
  • The C-rate current is a limit for the cell, not a target. Pack wiring, connectors and the protection board must also handle the current.
  • Lithium cells need a battery management system or protection board with balancing for series packs, and a charger made for that chemistry.

Common mistakes

  • Putting cells of different capacity or age in one pack.
  • Choosing a pack by capacity alone and ignoring the maximum current of the motors at stall.