FANUC Robot Fault Codes (SRVO, MOTN, INTP, SYST): Troubleshooting & Reset

FANUC R-30iB / R-30iA · OEM Fault Hub

FANUC Robot Fault Codes (SRVO, MOTN, INTP, SYST): Troubleshooting & Reset

Search FANUC SRVO, MOTN, INTP, and SYST alarm codes, pulse coder BZAL battery recovery, and Zero Position Mastering steps.

Showing 10 of 10 FANUC OEM fault codes

FANUC · SRVO-001 Operator Panel E-Stop
Critical E-Stop

Root Cause: Operator panel emergency stop button pressed or broken NC contact on E-stop loop.

Recovery Steps: Twist-release E-stop button, verify dual-channel 24V continuity on EES1/EES2 terminals, then press RESET.

Safety Interlock: Confirm cell perimeter is clear before resetting safety relay.

FANUC · SRVO-002 Teach Pendant E-Stop
Critical E-Stop

Root Cause: Teach pendant E-stop switch engaged or damaged pendant cable wiring.

Recovery Steps: Release teach pendant E-stop, inspect pendant connector pins, and press RESET on SOP/TP.

Safety Interlock: Never bypass pendant deadman or E-stop circuits.

FANUC · SRVO-003 Deadman Switch Released
Safety/I-O

Root Cause: Teach pendant is enabled in T1/T2 mode while the 3-position deadman switch is released or squeezed too hard.

Recovery Steps: Hold the deadman switch lightly at its center position before jogging or pressing RESET.

Safety Interlock: In T1 mode speed is limited to 250 mm/s for operator safety.

FANUC · SRVO-021 SRDY Off (Servo Not Ready)
Servo/Drive

Root Cause: Servo amplifier failed to energize or blown DC link fuse / contactor fault.

Recovery Steps: Inspect 3-phase input voltage, servo amp status LEDs, and emergency stop board fuses (F1/F2).

Safety Interlock: Wait 5 minutes after power off for DC bus capacitors to discharge.

FANUC · SRVO-023 Stop Error Excess
Motion/Collision

Root Cause: Axis failed to reach commanded target within servo lag tolerance due to mechanical jam, brake not releasing, or overload.

Recovery Steps: Inspect axis for tooling collision, check 90V/24V brake release voltage, and verify payload settings.

Safety Interlock: Support heavy vertical axes before mechanically releasing motor brakes.

FANUC · SRVO-050 Collision Detect Alarm
Motion/Collision

Root Cause: Motor disturbance torque exceeded disturbance threshold from impact or tight cable dress pack.

Recovery Steps: Switch to T1, jog carefully away from obstacle, inspect EOAT alignment, and adjust collision guard sensitivity if false trip.

Safety Interlock: Verify TCP and fixture zero after any physical impact.

FANUC · SRVO-062 BZAL (Battery Zero Alarm)
Servo/Drive

Root Cause: Pulse coder backup batteries depleted below 2.6V while controller power was off.

Recovery Steps: Replace 4x D-cell alkaline batteries with controller powered ON, reset pulse coder alarm, and perform Zero Position Mastering.

Safety Interlock: Always replace encoder batteries while main power is ON to preserve mastering.

FANUC · SRVO-068 DTERR (Serial Pulse Coder Data Error)
Servo/Drive

Root Cause: Noise or broken differential pair on motor pulsecoder feedback cable inside robot arm harness.

Recovery Steps: Inspect M12/Honda feedback connectors, shield grounding, and continuity of SD/REQ pairs in internal dress pack.

Safety Interlock: Lock out main disconnect before unplugging servo amplifier connectors.

FANUC · SRVO-105 Door Open / Fence Open
Safety/I-O

Root Cause: Safety gate interlock (EAS1/EAS2) opened while controller was in AUTO mode.

Recovery Steps: Close all safety gates, verify dual-channel interlock switch alignment, reset external safety relay, and press RESET.

Safety Interlock: Perform full cell sweep prior to re-arming AUTO.

FANUC · INTP-127 Power Fail Detected / Program Aborted
Servo/Drive

Root Cause: Brief AC mains sag or uncommanded power loss during motion execution.

Recovery Steps: Inspect plant 3-phase supply voltage, UPS/line reactor health, clear fault, and run recovery path.

Safety Interlock: Check part grip state before resuming cycle.

FANUC BZAL Reset & Zero Position Mastering Procedure

  1. Keep main controller power ON when replacing the 4x D-cell 6V pulse coder battery pack in the robot base to avoid losing mastering.
  2. Press MENU -> SYSTEM -> Master/Cal (if hidden, set system variable $MASTER_ENB = 1).
  3. To clear SRVO-062 BZAL / SRVO-038: press F3 RES_PCA -> YES, then cycle controller power.
  4. Jog all axes to their physical Zero-Degree witness marks in JOINT mode (T1 <= 250 mm/s) and select ZERO POSITION MASTER -> F4 YES.
  5. Execute CALIBRATE -> F4 YES and verify TCP repeatability on a known reference pointer before switching back to AUTO.
Grow Your Robotics / Automation Brand Online with Jaadu Digital Technical SEO, B2B lead generation, and engineering content systems built for robotics integrators and OEMs.
Explore Jaadu Digital →

Frequently Asked Engineering Questions

How do I clear FANUC SRVO-062 BZAL without losing calibration?

Replace the 4x D-cell alkaline batteries in the manipulator base with controller power ON, open SYSTEM -> Master/Cal, execute RES_PCA, cycle power, and jog to witness marks if zero reference was already lost.

What causes FANUC SRVO-050 Collision Detect false trips?

False SRVO-050 alarms commonly occur when actual EOAT mass or CoG offsets do not match SYSTEM -> Motion Payload Setup, or when a stiff hose dress pack snags during wrist rotation.

How do I reset FANUC SRVO-001 or SRVO-105 safety fence alarms?

Verify dual-channel 24V continuity across EES1/EES2 or EAS1/EAS2 on the emergency stop board, close safety gates, reset the external safety relay, and press RESET on the iPendant.

Wrist Kinematics · Static + Dynamic Moment + Inertia J

Robot Payload, Wrist Torque & Inertia Calculator

PASS — Within Envelope
Total Flange Mass
6.60 kg (66%)
Static Wrist Moment
10.28 Nm
Peak Combined Torque (SF)
33.90 Nm
Flange Inertia J
0.219 kg·m²
J6 Flange Axial Z = 145 mm Radial XY = 65 mm Total Mass: 6.60 kg | Peak Torque: 33.90 Nm Effective J: 0.219 kg·m²
Grow Your Robotics / Automation Brand Online with Jaadu Digital Technical SEO, B2B lead generation, and engineering content systems built for robotics integrators and OEMs.
Explore Jaadu Digital →

Frequently Asked Engineering Questions

Why can a 10 kg rated robot overload with only a 6 kg gripper and part?

Catalog payload ratings assume a short CoG offset (often 80–100 mm). Long cantilevered tooling or high linear/angular accelerations exceed the rated wrist torque (Nm) and inertia (kg·m²) before total mass hits 10 kg.

How is effective mass moment of inertia J calculated at the flange?

By the parallel-axis theorem: J = I_cm + m * r², where I_cm is the load inertia about its own center of mass, m is total flange mass, and r is the 3D CoG distance from the wrist axis.

What safety factor should I use for dynamic robot payload sizing?

Use 1.25x for steady pick-and-place, 1.4x for high-speed palletizing or E-stop deceleration, and 1.5x+ when handling eccentric castings or vacuum-gripped sheet metal.

Does entering wrong payload data affect robot accuracy and brake wear?

Yes. Wrong payload mass or CoG causes overshoot, false collision trips, premature harmonic-drive wear, and longer stopping distances during Category 1 safety stops.

How do I reduce wrist torque without buying a larger robot?

Move heavy solenoid valves and vacuum generators off the EOAT onto the upper arm, shorten flange standoffs, and align the heaviest part dimension along the J6 rotation axis.