Industrial Robot Fault Code Finder (FANUC, ABB, KUKA, Yaskawa, UR)

Use this engineering reference to diagnose 50 high-frequency servo, collision, encoder battery, and dual-channel safety alarms across FANUC, ABB, KUKA, Yaskawa Motoman, and Universal Robots controllers.

50 OEM Fault Codes

Industrial Robot Fault Code Finder & Recovery Guide

Filter across FANUC, ABB, KUKA, Yaskawa Motoman & Universal Robots alarms by brand, keyword, or fault category.

Showing 50 of 50 OEM fault codes

FANUC · SRVO-001 Operator Panel E-Stop
Critical E-Stop

Root Cause: Operator panel emergency stop button pressed or broken NC contact on E-stop loop.

Recovery Steps: Twist-release E-stop button, verify dual-channel 24V continuity on EES1/EES2 terminals, then press RESET.

Safety Interlock: Confirm cell perimeter is clear before resetting safety relay.

FANUC · SRVO-002 Teach Pendant E-Stop
Critical E-Stop

Root Cause: Teach pendant E-stop switch engaged or damaged pendant cable wiring.

Recovery Steps: Release teach pendant E-stop, inspect pendant connector pins, and press RESET on SOP/TP.

Safety Interlock: Never bypass pendant deadman or E-stop circuits.

FANUC · SRVO-003 Deadman Switch Released
Safety/I-O

Root Cause: Teach pendant is enabled in T1/T2 mode while the 3-position deadman switch is released or squeezed too hard.

Recovery Steps: Hold the deadman switch lightly at its center position before jogging or pressing RESET.

Safety Interlock: In T1 mode speed is limited to 250 mm/s for operator safety.

FANUC · SRVO-021 SRDY Off (Servo Not Ready)
Servo/Drive

Root Cause: Servo amplifier failed to energize or blown DC link fuse / contactor fault.

Recovery Steps: Inspect 3-phase input voltage, servo amp status LEDs, and emergency stop board fuses (F1/F2).

Safety Interlock: Wait 5 minutes after power off for DC bus capacitors to discharge.

FANUC · SRVO-023 Stop Error Excess
Motion/Collision

Root Cause: Axis failed to reach commanded target within servo lag tolerance due to mechanical jam, brake not releasing, or overload.

Recovery Steps: Inspect axis for tooling collision, check 90V/24V brake release voltage, and verify payload settings.

Safety Interlock: Support heavy vertical axes before mechanically releasing motor brakes.

FANUC · SRVO-050 Collision Detect Alarm
Motion/Collision

Root Cause: Motor disturbance torque exceeded disturbance threshold from impact or tight cable dress pack.

Recovery Steps: Switch to T1, jog carefully away from obstacle, inspect EOAT alignment, and adjust collision guard sensitivity if false trip.

Safety Interlock: Verify TCP and fixture zero after any physical impact.

FANUC · SRVO-062 BZAL (Battery Zero Alarm)
Servo/Drive

Root Cause: Pulse coder backup batteries depleted below 2.6V while controller power was off.

Recovery Steps: Replace 4x D-cell alkaline batteries with controller powered ON, reset pulse coder alarm, and perform Zero Position Mastering.

Safety Interlock: Always replace encoder batteries while main power is ON to preserve mastering.

FANUC · SRVO-068 DTERR (Serial Pulse Coder Data Error)
Servo/Drive

Root Cause: Noise or broken differential pair on motor pulsecoder feedback cable inside robot arm harness.

Recovery Steps: Inspect M12/Honda feedback connectors, shield grounding, and continuity of SD/REQ pairs in internal dress pack.

Safety Interlock: Lock out main disconnect before unplugging servo amplifier connectors.

FANUC · SRVO-105 Door Open / Fence Open
Safety/I-O

Root Cause: Safety gate interlock (EAS1/EAS2) opened while controller was in AUTO mode.

Recovery Steps: Close all safety gates, verify dual-channel interlock switch alignment, reset external safety relay, and press RESET.

Safety Interlock: Perform full cell sweep prior to re-arming AUTO.

FANUC · INTP-127 Power Fail Detected / Program Aborted
Servo/Drive

Root Cause: Brief AC mains sag or uncommanded power loss during motion execution.

Recovery Steps: Inspect plant 3-phase supply voltage, UPS/line reactor health, clear fault, and run recovery path.

Safety Interlock: Check part grip state before resuming cycle.

ABB · 10010 Motors Off State / Guard Stop
Safety/I-O

Root Cause: Controller entered Motors Off due to Auto Stop, General Stop, or safety chain interruption.

Recovery Steps: Close cell gates, verify AS1/AS2 and GS1/GS2 LEDs on safety board, then press Motors On pushbutton.

Safety Interlock: Verify dual-channel safety integrity if fault repeats.

ABB · 20010 Emergency Stop Reset Required
Critical E-Stop

Root Cause: Emergency stop circuit was opened and subsequently closed, awaiting explicit reset.

Recovery Steps: Confirm E-stop buttons are released and press Reset / Motors On button on FlexPendant or cabinet.

Safety Interlock: Never auto-reset E-stop without physical inspection.

ABB · 20201 Limit Switch / Axis Overtravel
Motion/Collision

Root Cause: Joint exceeded configured software or hardware travel limit during jog or program move.

Recovery Steps: Jog axis back inside software limits using joint coordinate mode; inspect hard stops if triggered.

Safety Interlock: Check workobject frame offsets if occurring in AUTO.

ABB · 38200 SMB Battery Charge Low
Servo/Drive

Root Cause: Serial Measurement Board (SMB) lithium backup battery voltage dropped near warning threshold.

Recovery Steps: Order and replace SMB battery inside manipulator base with power ON, then verify revolution counters.

Safety Interlock: Update revolution counters immediately if power was lost while depleted.

ABB · 50050 Position Out of Reach
Motion/Collision

Root Cause: Target RobTarget lies outside kinematic reach or wrist singularity envelope.

Recovery Steps: Adjust target coordinates, ConfL/ConfJ configuration flags, or base/tool frame definition.

Safety Interlock: Simulate modified path in T1 low speed first.

ABB · 50056 Joint Collision / Torque Supervision
Motion/Collision

Root Cause: Estimated external torque exceeded motion supervision threshold on one or more axes.

Recovery Steps: Clear physical obstruction, inspect part weight vs LoadData, and recalibrate LoadIdentify if tooling changed.

Safety Interlock: Inspect gearbox backlash after hard stops.

ABB · 50204 Motion Supervision Triggered
Motion/Collision

Root Cause: High acceleration against heavy inertia or sudden contact caused drive torque trip.

Recovery Steps: Verify accurate mass and center-of-gravity in tool0/tooldata and reduce AccSet ramp if needed.

Safety Interlock: Check gripper mounting bolts for shear or loosening.

ABB · 50296 Drive Unit DC Link Undervoltage
Servo/Drive

Root Cause: Mains phase drop, blown rectifier fuse, or loose contactor on DC bus distribution.

Recovery Steps: Measure L1-L2-L3 mains voltage under load and check main contactor K1/K2 coil and contacts.

Safety Interlock: Follow lockout-tagout and capacitor discharge wait time.

ABB · 50357 Corner Path Failure
Motion/Collision

Root Cause: Program pointer could not compute zone blend ahead due to WaitDI/logic blocking Lookahead.

Recovery Steps: Adjust zone data (z10/z50) or insert WaitTime/InPos synchronization before I/O reads.

Safety Interlock: Verify clearance around blend corner before increasing zone radius.

ABB · 71058 PROFINET / Fieldbus I/O Comm Lost
Safety/I-O

Root Cause: PLC fieldbus cable unplugged, IP conflict, or switch port link drop interrupting cyclic I/O.

Recovery Steps: Inspect RJ45/M12 patch cord, check PLC Device Name & GSDML status, and warm-restart I/O bus.

Safety Interlock: Ensure safe outputs fail to de-energized state on bus loss.

KUKA · KSS00404 Safety Stop (External Safe Stop)
Safety/I-O

Root Cause: External safety stop input (SIB / ProfiSafe / CIP Safety) dropped to FALSE.

Recovery Steps: Verify light curtain alignment, gate switches, and safety PLC Stop_Ext bit status, then acknowledge messages.

Safety Interlock: Do not bridge safety PLC signals during troubleshooting.

KUKA · KSS01031 Torque / Gear Monitoring Axis
Motion/Collision

Root Cause: Actual motor current exceeded dynamic model envelope due to collision or stiff dress pack.

Recovery Steps: Jog clear in T1, inspect hose/cable package interference, and verify $LOAD data matches actual payload.

Safety Interlock: Inspect wrist flange bolts and tool changer lock.

KUKA · KSS01105 Software Limit Switch Reached
Motion/Collision

Root Cause: Commanded joint angle hit $SOFTN_END or $SOFTP_END boundary.

Recovery Steps: Switch to Axis jogging in T1 and move joint back inside $SOFTN_END..$SOFTP_END limits.

Safety Interlock: Check tool orientation if hit near wrist A5/A6.

KUKA · KSS01425 Mastering Lost on Axis
Servo/Drive

Root Cause: Resolver mastering reference lost due to dead RDC backup batteries or motor/cable swap.

Recovery Steps: Replace KRC cabinet batteries if low and perform EMT/MEMD mastering on the affected axis.

Safety Interlock: Never run production programs with unmastered axes.

KUKA · KSS12016 Active Commands Inhibited
Safety/I-O

Root Cause: A higher-priority stop condition (Operator Safety, E-stop, or Drives Off) blocks motion enable.

Recovery Steps: Read preceding KSS alarm in SmartHMI message window, clear root safety stop, and enable drives.

Safety Interlock: Always resolve root safety message before acknowledging.

KUKA · KSS15002 Safe Device Communication Error
Safety/I-O

Root Cause: CIP Safety or ProfiSafe cyclic watchdog timed out between PLC and KRC4/KRC5.

Recovery Steps: Inspect industrial Ethernet switch port diagnostics, safety timeout setting, and F-address match.

Safety Interlock: Verify safety network cable shielding away from VFD motor leads.

KUKA · KSS15004 Mastering Test Required (Safety)
Safety/I-O

Root Cause: KUKA SafeOperation brake/mastering reference test interval expired.

Recovery Steps: Run the scheduled Mastering Test reference run in T1/EXT against the reference switch fork.

Safety Interlock: Required to maintain SIL2/PLd safe workspace monitoring.

KUKA · KSS26006 KPP DC Bus Overvoltage
Servo/Drive

Root Cause: Excessive regenerative energy during rapid downward deceleration or failed braking resistor.

Recovery Steps: Measure braking chopper resistor resistance (ohms) and verify deceleration ramp limits.

Safety Interlock: Resistor surface can exceed 150C; allow cooling before inspection.

KUKA · KSS00203 General Motion Enable Missing
Safety/I-O

Root Cause: $MOVE_ENABLE signal from cell PLC is FALSE in EXT mode.

Recovery Steps: Check PLC handshake output mapped to $MOVE_ENABLE and verify cell cycle-ready state.

Safety Interlock: Confirm robot is in safe home window before PLC re-enables motion.

KUKA · KSS03121 Workspace Envelope Violated
Motion/Collision

Root Cause: TCP entered a forbidden Cartesian $WORKSPACE or SafeOperation protection zone.

Recovery Steps: Jog out of restricted zone in T1 and review tool TCP offsets and base calibration.

Safety Interlock: Confirm physical guarding matches configured safe zone coordinates.

Yaskawa · Alarm 1300 CPU / Servo Communication Error
Servo/Drive

Root Cause: Faulty servo pack link cable or EMI noise between YRC1000/DX200 main CPU and SERVOPACK.

Recovery Steps: Power cycle controller, inspect internal SERCOS/MECHATROLINK fiber/bus connectors, and verify grounding.

Safety Interlock: Check earth resistance (<100 ohm) in high-noise welding cells.

Yaskawa · Alarm 1326 Encoder Battery Voltage Low
Servo/Drive

Root Cause: Manipulator base encoder backup battery pack falling below minimum retention voltage.

Recovery Steps: Replace Yaskawa encoder battery pack while controller is powered ON, then clear alarm.

Safety Interlock: Powering down before replacement causes loss of home position.

Yaskawa · Alarm 4100 Overload (Motor Thermal / Torque)
Servo/Drive

Root Cause: Continuous RMS motor current exceeded servo pack thermal model due to excess payload or friction.

Recovery Steps: Verify payload weight & CoG settings, inspect reducer lubrication, and reduce duty cycle or speed.

Safety Interlock: Allow motor/drive to cool before restarting heavy cycle.

Yaskawa · Alarm 4110 Shock Sensor / Collision Detected
Motion/Collision

Root Cause: External shock sensor or software shock detection level tripped on sudden impact.

Recovery Steps: Switch to TEACH mode, release shock sensor reset, jog clear, and inspect torch/gripper alignment.

Safety Interlock: Re-verify TCP with pointer gauge after collision.

Yaskawa · Alarm 4207 System Error (Servo Tracking)
Motion/Collision

Root Cause: Following error exceeded limit during rapid acceleration or mechanical binding.

Recovery Steps: Inspect brake release supply, check axis interference, and verify payload inertia parameter.

Safety Interlock: Test motion at 25% teach speed before returning to PLAY.

Yaskawa · Alarm 4315 Collision Detection (High Sensitivity)
Motion/Collision

Root Cause: Software disturbance observer sensed unexpected resistance along programmed trajectory.

Recovery Steps: Inspect cable dress pack snagging, recalibrate tool weight/inertia, and tune shock level file.

Safety Interlock: Do not disable shock detection on unguarded cells.

Yaskawa · Alarm 4401 Servo On Impossible (Safety Chain)
Critical E-Stop

Root Cause: Dual-channel E-stop or safeguard circuit open when Servo On was requested.

Recovery Steps: Check pendant E-stop, external E-stop terminals, and safety relay board LEDs before pressing Servo On.

Safety Interlock: Inspect both A and B channels for single-channel weld faults.

Yaskawa · Alarm 4511 Over Speed / Command Velocity Limit
Servo/Drive

Root Cause: Commanded joint speed exceeded motor maximum RPM near wrist singularity.

Recovery Steps: Re-orient tool slightly away from A4/A6 collinear singularity or convert linear move to MOVJ.

Safety Interlock: Verify safe speed limit in Teach mode.

Yaskawa · Alarm 4980 Out of Range (Home Position Check)
Servo/Drive

Root Cause: Absolute encoder position differs from stored second home check position by more than tolerance.

Recovery Steps: Jog robot to alignment scribe marks, verify mechanical zero, and execute Second Home Position reset.

Safety Interlock: Never overwrite home position without verifying physical witness marks.

Yaskawa · Alarm 9000 External User Alarm / PLC Hold
Safety/I-O

Root Cause: User-defined ladder logic or external PLC raised an application fault (gripper timeout, part missing).

Recovery Steps: Inspect CIO ladder alarm description and field sensor (prox/vacuum switch) state on the fixture.

Safety Interlock: Check pneumatic pressure before resetting gripper fault.

Universal Robots · C153 Joint Position Deviation / Protective Stop
Motion/Collision

Root Cause: Joint deviated from target trajectory due to collision, tight cable, or wrong payload setting.

Recovery Steps: Verify exact TCP and Payload (mass + CoG) in Installation settings, inspect path, and tap Enable Robot.

Safety Interlock: Confirm human collaborator is clear of pinch point.

Universal Robots · C157 Collision / Excess External Force
Motion/Collision

Root Cause: Estimated force/torque breached ISO/TS 15066 safety limit on joint current sensors.

Recovery Steps: Clear contact, review Safety -> Robot Limits (Normal/Reduced mode), and verify part presentation tolerance.

Safety Interlock: Re-validate collaborative risk assessment if increasing force limits.

Universal Robots · C175 Safety System Fault (Dual Channel)
Critical E-Stop

Root Cause: Discrepancy >500ms between Channel A and Channel B on Emergency Stop or Safeguard Stop inputs.

Recovery Steps: Inspect E-stop wiring for loose terminal or single-channel contact bounce; perform Complete Reboot.

Safety Interlock: Replace defective dual-channel switch before resuming.

Universal Robots · C186 Joint Motor Current High
Servo/Drive

Root Cause: Sustained current near joint thermal limit from heavy cantilevered EOAT or high duty cycle.

Recovery Steps: Reduce CoG offset, add brief dwell or lower acceleration, and check ambient enclosure temperature.

Safety Interlock: Verify payload is within cobot wrist torque curve.

Universal Robots · C191 Safety Plane / Tool Orientation Violated
Safety/I-O

Root Cause: Elbow, wrist, or tool sphere crossed configured Safety Plane or cone orientation limit.

Recovery Steps: Use Freedrive to move arm safely inside allowed zone, then adjust waypoints with margin.

Safety Interlock: Do not widen safety planes without checking operator reach.

Universal Robots · C204 Payload Exceeds Safety Limit
Motion/Collision

Root Cause: Measured dynamic torque mismatches declared payload or exceeds configured safety payload ceiling.

Recovery Steps: Use UR Payload Estimation wizard with actual EOAT + heaviest workpiece and update Installation.

Safety Interlock: Wrong payload triggers false stops and risks safety compliance.

Universal Robots · C207 Brake Release / Joint Startup Failure
Servo/Drive

Root Cause: Joint electromagnetic brake failed to disengage during Initialization due to external torque or 48V sag.

Recovery Steps: Support arm weight manually, re-initialize robot, and verify 48V PSU voltage under startup load.

Safety Interlock: Ensure tool is not resting heavily against a fixture during boot.

Universal Robots · C209 48V Power Supply Fault
Servo/Drive

Root Cause: Control box internal 48V DC power supply overcurrent, undervoltage, or regenerative surge.

Recovery Steps: Power cycle control box, inspect Energy Eater braking resistor, and check heavy downward deceleration.

Safety Interlock: Disconnect mains before opening control box.

Universal Robots · C253 Tool Communication / RS485 Error
Safety/I-O

Root Cause: Loose M8 tool connector or baud/voltage mismatch with electric gripper or force-torque sensor.

Recovery Steps: Check Tool I/O 24V/12V setting, inspect M8 8-pin connector pins, and verify URCap driver status.

Safety Interlock: Power off Tool I/O before mating or unmating M8 plug.

Universal Robots · C262 Safety PLC / PROFINET Safety Timeout
Safety/I-O

Root Cause: Loss of PROFIsafe or EtherNet/IP Safety heartbeat from cell safety controller.

Recovery Steps: Verify network switch link, safety PLC run state, and matching safety checksum/port config.

Safety Interlock: Cobot enters Safeguard Stop automatically until heartbeat stabilizes.

Grow Your Robotics / Automation Brand Online with Jaadu Digital Technical SEO, B2B lead generation, and engineering content systems built for robotics integrators and OEMs.
Explore Jaadu Digital →

Frequently Asked Engineering Questions

How do I clear a FANUC SRVO-021 or SRVO-062 pulse coder alarm?

Never reset encoder or servo drive faults before checking input power and backup battery voltage. For SRVO-062 (BZAL), replace the 6V battery pack with controller power ON, then master and calibrate the affected axis before resuming production.

Why does an ABB IRC5 or OmniCore robot throw Event 50056 or 50204?

ABB motion supervision (50204) triggers when motor torque exceeds the collision model due to tooling contact, incorrect payload data, or stiff dress packs. Joint load errors (50056) require verifying payload mass, center of gravity, and inertia settings.

What causes KUKA KSS01422 or KSS15002 safety stop faults?

Safety-circuit and mastering alarms on KUKA KRC4/KRC5 controllers usually stem from dual-channel X11/CIP Safety mismatch, loose RDC data cables, or low DC bus voltage during regenerative braking.

How should engineers handle Yaskawa Alarm 4100 or 4310 overload faults?

Verify servo motor U/V/W phase continuity, brake release voltage (24V/90V DC), mechanical gearbox binding, and duty cycle thermal load before resetting the Motoman YRC1000 alarm.

What do Universal Robots C153/C204/C262 protective stop codes indicate?

UR e-Series protective stops indicate joint torque deviation, TCP force limit exceedance, or safety plane violation. Inspect payload CG configuration, wrist cable routing, and ISO/TS 15066 speed-and-separation zones.